TJK636500
* Actual product may vary from image
The J600 product line consists of Thermal Magnetic Circuit Breakers, Magnetic Circuit Breakers, and Molded-Case Switches rated up to 600 Amps and 600 Volts AC. These breakers are available with either non-interchangeable trips (designated type TJJ) or interchangeable trips (designated types TJK/THJK). Type TJJ devices ship fully assembled while types TJK/THJK ship unassembled unless specified on the order. TJK breakers are available in two frames, 400 ampere frame (125 to 400 amperes) and 600 ampere frame (250 to 600 amperes). Trip units are not interchangeable between frames. The WL catalog number suffix indicates that the devices come with Cu/Al line and load lugs. TJK6 3 POLE 600V 500 AMP
Details
MFG PART #:TJK636500
TRC Part #:GEDITJK636500
UPC #:783164050783
Inventory
$7,048.00Â E
Details
MFG PART #:TJK636500
TRC Part #:GEDITJK636500
UPC #:783164050783
Inventory
Attributes
Features
Documentation
Attributes
Actuator Type:Toggle
Amperage Rating:500 A
Connection Type:Load Lug
Dimensions:10-1/8 in H x 8-1/4 in W x 3-13/16 in D
Frame:J600
Frequency Rating:50/60 Hz
Interrupt Rating:20/22/30/42 kA
Material:Plastic
Mounting Type:Bolted-On
Number Of Poles:3
Phase:3
Temperature Rating:10 to 50 deg C
Trip Type:Interchangeable/Thermal Magnetic/LI
Type:Type TJK Core J
Voltage Rating:600 VAC
Trip Range:1500 to 5000 A
Features
Molded case is molded from high mechanical and high dielectric strength engineered plastic |
Trip indication is shown by handle position midway between ON and OFF, to reset the trip mechanism, move the handle to extreme OFF, then to ON position |
Quick make, quick break, trip free mechanism minimizes arcing during breaker operation, contacts cannot be ''teased'' into position |
Trip free mechanism is independent of manual handle control, the breaker trips under short circuit or overload, even though the operating handle is held in ON position |
VERIFIERâ„¢ "Twist-to-Trip" and ''Push-to-Trip'' mechanically simulates over current tripping through actuation of linkages not operated by the ON/OFF handle |
Common trip bar assures instant disconnect of all conductors when an overload or short circuit occurs on any one conductor in the circuit or an accessory trip device operates |
Silver alloy contacts combine the conductive properties of silver with other elements for clean, positive electrical contacting, pitting and burning are minimized for longer contact life |
Arc chutes of heat absorbing, insulating material and metal grid plates quickly ''extinguish'' arcs |
UL Listed lugs for copper or aluminum cable, at full frame rating, easy access and simple, straight-in wiring |
20 kA at 125 VDC, 20 kA at 250 VDC, 20 kA at 500 VDC, 22 kA at 600 VAC, 30 kA at 277 VAC, 30 kA at 480 VAC, 42 kA at 120 VAC, 42 kA at 120/240 VAC, 42 kA at 240 VAC interrupt rating |