DSW-301-I
WattStopper®* Actual product may vary from image
The DSW-301 Dual Technology Wall Switch Occupancy Sensor turns lights OFF and ON based on occupancy. It combines the benefits of passive infrared (PIR) and ultrasonic detection technologies. The DSW-301 replaces existing wall switches and fits behind a standard decorator wall plate. (ivory)
Details
MFG PART #:DSW-301-I
TRC Part #:WASTDSW301I
UPC #:754182935413
Inventory
$120.07 E
Details
MFG PART #:DSW-301-I
TRC Part #:WASTDSW301I
UPC #:754182935413
Inventory
Attributes
Features
Documentation
Attributes
Brand:WattStopper®
Type:Dual Technology Dual Relay
Series:DSW
Voltage Rating:120/277 VAC
Power Rating:0 to 1200 W, 1/6 hp
Sensor Type:Passive Infrared/Ultrasonic
Coverage:1050 sq-ft
Viewing Angle:180 deg
Time Delay:5 to 30 min
Lamp Type:LED
Connection Type:Flying Lead
Control Output:Automatic On/Off, Manual On/Off
Mounting Type:Surface
Temperature Rating:35 deg C
Material:Plastic
Color:Ivory
Dimensions:2.73 in L x 1.75 in W x 1.81 in H
Features
Time delay adjustments - 5 to 30 min at minimum, 3 minimum if no activity after 30 s at walk through mode, 5 s for 10 min with dip switch setting at test mode |
High or low (dip switch) PIR adjustment and minimum to maximum (trimpot), OFF ultrasonic adjustment |
1000 W tungsten, ballast, E-ballast, LED, 1/4 hp load limit for relay 1 at 120 VAC, 1200 W ballast, E-ballast, LED, 1/4 hp load limit for relay 1 at 277 VAC, 800 W tungsten, ballast, E-ballast, LED, 1/6 hp load limit for relay 2 at 120 VAC, 1200 W ballast, E-ballast, LED, 1/6 hp load limit for relay 2 at 277 VAC |
Complies with 2011 NEC requirements |
Zero crossing for long relay life |
Vandal-resistant lens combines precise coverage with durability |
Selectable walk through mode turns lights off 3 minutes after the room is initially occupied if no motion is detected after the first 30 s |
Test mode allows quick and easy adjustments |
Selectable audible alert for impending shutoff |
In automatic mode, sensor returns automatically to auto-ON after lights are turned OFF manually, ideal for presentations |