APPEYDM300
Appleton®* Actual product may vary from image
Appleton UNILETS EYDM Series 25 PCT Fill Vertical Conduit Drain Sealing Fitting With Removable Nipple, Size: 3 IN, Material: Malleable Iron, Finish: Triple-Coat (Zinc Electroplate, Chromate And Epoxy Powder Coat), Connection: Tapered MNPT X Tapered FNPT, Turning Radius: 3.13 IN, Length: 8.13 IN, Width: 4.13 IN, Standard: UL 886 (1203), UL File Number E10444, CSA C22.2 No. 30, CSA 065181, UL Listed For Class I, Groups B, C, D, Class II, Groups E, F, G, And Class III, For Use With Threaded Rigid Metal Conduit and IMC
Details
MFG PART #:APPEYDM300
TRC Part #:EGSMEYDM300
UPC #:781381230223
Inventory
$382.98 E
Details
MFG PART #:APPEYDM300
TRC Part #:EGSMEYDM300
UPC #:781381230223
Inventory
Attributes
Features
Documentation
Attributes
Brand:Appleton®
Type:Dust-Ignitionproof Explosionproof Raintight
Series:EYDM
Size:3 in
Suitable For Use With:IMC/Threaded Rigid Metallic Conduit
Material:Malleable Iron
Finish:Triple Coated
Dimensions:8.13 in L x 4.13 in W
Features
Smooth, rounded integral bushing in each hub to protect conductor insulation |
Accurately tapped, tapered NPT threads for tight, rigid joints and ground continuity |
Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub |
Close radius type for sealing vertical conduit runs |
Restrict any explosion to the sealed off enclosure |
Required in Class I, Division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures |
Required in Class I, Division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps |
Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location |
Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit, seal must be located within 18 in of either enclosure |
Required where cables which exceed rate of gas or vapor transmission permitted for seals are used in Class I, Division 2 locations |