THQL21125
GE* Actual product may vary from image
Q Line circuit breakers are one-inch wide per pole, compact, thermal-magnetic devices designed for residential and commercial applications in load centers or lighting panels. All Q Line circuit breakers feature Quick-make / Quick-break mechanisms, common trip bars, and easy to spot trip indication to ensure safety and reliability. Q Line breakers can be ordered with auxiliary contact and shunt trip accessories, and can be ordered for use in HID applications. THQL21125 breaker features 2 poles, an ampere rating of 125 A, an interrupting rating of 10kAIC, and a voltage rating of 120/240V.
Details
MFG PART #:THQL21125
TRC Part #:GEDITHQL21125
UPC #:783164081909
Inventory
$ E
Details
MFG PART #:THQL21125
TRC Part #:GEDITHQL21125
UPC #:783164081909
Inventory
Attributes
Features
Documentation
Attributes
Brand:GE
Type:Type THQL Compact
Voltage Rating:120/240 VAC
Amperage Rating:125 A
Frequency Rating:50/60 Hz
Interrupt Rating:10 kA
Frame:Q-Line
Trip Type:Non-Interchangeable Thermal Magnetic/LI
Number of Poles:2
Phase:1
Actuator Type:Pivot/Toggle Handle
Connection Type:Load Lug
Wire Size:2 to 2/0 AWG
Mounting Type:Plug-In
Temperature Rating:10 to 50 deg C
Dimensions:3-9/32 in H x 2 in W x 2-3/8 in D
Material:Plastic
Features
Molded case is molded from high mechanical and high dielectric strength engineered plastic |
Trip indication is shown by handle position midway between ON and off to reset the trip mechanism, move the handle to extreme off then to ON position |
Quick-make, quick-break, trip-free mechanism minimizes arcing during breaker operation, contacts cannot be ''teased'' into position |
Trip-free mechanism is independent of manual handle control, the breaker trips under short circuit or overload, even though the operating handle is held in on position |
VERIFIER™ "twist-to-trip" and ''push-to-trip'' mechanically simulates over current tripping through actuation of linkages not operated by the on-off handle |
Common trip bar assures instant disconnect of all conductors when an overload or short circuit occurs on any one conductor in the circuit or an accessory trip device operates |
Silver alloy contacts combine the conductive properties of silver with other elements for clean, positive electrical contacting, pitting and burning are minimized for longer contact life |
Arc chutes of heat absorbing, insulating material and metal grid plates quickly ''extinguish'' arcs |
UL listed lugs for copper or aluminum cable, at full frame rating, easy access and simple, straight in wiring |
10 kA at 120 VAC, 10 kA at 120/240 VAC interrupt rating |