TM42422C
GE* Actual product may vary from image
Main breaker load centers arrive with a main breaker installed for a convenient and swift install. Main breakers allow for the user to stop the flow of electricity in the load center, shutting off all the power in the residence. The TM42422C features spaces for 42, 1" breakers, a 225A main ampere rating, 3 phases, and a combination surface/flush enclosure.
Details
MFG PART #:TM42422C
TRC Part #:GEDITM42422C
UPC #:783164190052
Inventory
$ E
Details
MFG PART #:TM42422C
TRC Part #:GEDITM42422C
UPC #:783164190052
Inventory
Attributes
Features
Documentation
Attributes
Brand:GE
Amperage Rating:225 A
Breaker Type:THQL
Dimensions:43-7/16 in H x 14 in W x 4-5/8 in D
Enclosure Box Size:NEMA 15
Enclosure Type:NEMA 1
Interrupt Rating:22 kA
Mounting Type:Flush
Number of Circuits:42
Number of Poles:1
Number of Spaces:62
Type:3-Phase Standard
Voltage Rating:208Y/120 V AC, 208Y/120 VAC
Wire Size:1 AWG to 300 kcmil, 2/0 AWG to 300 kcmil
Wiring Configuration:4-Wire
Features
| Suitable for use as service entrance equipment when installed in accordance with the national electrical Code® |
| 6 to 42 circuit devices UL listed for bottom mounted lug by installing complete unit box, interior and front upside down |
| 60 to 70 deg C conductor rating |
| Main lug models field convertible to main breaker |
| Split neutrals extend the full length of the interior for ease of wiring |
| Entire main lug line converts easily to main breaker |
| Front packed in inner carton for added protection |
| Straight through main wiring |
| Compact box maintains optimum wire bending space |
| Top feed |