FD63B090
Siemens* Actual product may vary from image
SIEMENS LOW VOLTAGE SENTRON MOLDED CASE CIRCUIT BREAKER WITH THERMAL - MAGNETICTRIP UNIT. UN-ASSEMBLED STANDARD 40 DEG C BREAKER FD FRAME WITH STANDARD BREAKING CAPACITY. 90A 3-POLE (22KAIC AT 600V) (35KAIC AT 480V). INTERCHANGEABLE TRIP UNIT. SPECIAL FEATURES LINE AND LOAD SIDE LUGS (TA1FD350A) WIRE RANGE 6AWG - 350KCMIL (CU) / 4AWG - 350KCMIL (AL). DIMENSIONS (W x H x D) IN 4.50 x 9.5 x 4.00.
Details
MFG PART #:FD63B090
TRC Part #:SIEMFD63B090
UPC #:783643211438
Inventory
$Â E
Details
MFG PART #:FD63B090
TRC Part #:SIEMFD63B090
UPC #:783643211438
Inventory
Attributes
Features
Documentation
Attributes
Brand:Siemens
Amperage Rating:90 A
Connection Type:Load Lug
Dimensions:7 in L x 6 in W x 11 in H
ETIM:EC000228
Frame:FD6
Frequency Rating:50/60 Hz
Interrupt Rating:22 kA
Number of Poles:3
Phase:3
Temperature Rating:40 deg C
Trip Range:640 to 900 A
Trip Type:Thermal/Magnetic
Type:Low Voltage
Voltage Rating:600 VAC/500 VDC
Features
| Molded case circuit breakers are used in motor circuits as a disconnecting means and for short circuit protection |
| They should be used in conjunction with motor running, over-current-protection devices, and should permit the motor to start without nuisance tripping from motor-inrush current |
| The circuit breaker should have a continuous current rating of not less than 115% of the motor full-load current |
| Actuator varying |
| Enclosure varying |
| Blue label |